รายละเอียดสินค้า: |
|
|
|
|
|
▪ Battery operated, low power consumption; |
▪ Ability of preventing disturbance from earth voltage; |
▪ Simplified Measurement function; |
▪ Battery check function. |
|
|
|
|
|
รายละเอียดทางด้านเทคนิค: |
|
|
|
▪ Measurement Ranges |
|
: Earth resistance: 10/100/1000 Ohms |
|
|
: Earth voltage: 30V AC |
▪ Acurracy |
|
: Earth resistance: 3% f.s. |
|
|
: Earth voltage: 3% f.s. |
▪ Measurement Systems |
: Earth resistance by constant current inverter 800Hz |
|
|
appox. 2mA |
|
|
: Earth voltage by rectifier type 5KOhms/V approx. 40-500Hz |
▪ Self-check Function |
|
: Lead wire connection to C and P terminals and proper |
|
|
auxiliary earth resistance can be check by pressing |
|
|
"BATT.CHECK" button. Lead wire connection to C and |
|
|
E terminals is good when "OK" indicator is lit. |
▪ Withstand Voltage |
|
: 1500V AC for 1 minute between circuit and case |
|
|
|
หมายเหตุ: กรุณาติดต่อบริษัทฯ เพื่อขอรับรายละเอียดสินค้าเพิ่มเติม |